Languages

LV ABC Cable

This cable is suitable for overhead power line of AC rated voltage Uo/U 0.6/1KV and below.

  • Product Details
  • FAQ
  • Reviews


Application

This is a kind of climate bearable PVC, HEPE and XLPE insulated aerial cables of copper core,aluminum core or aluminum alloy core, suitable for overhead power line of AC rated voltage Uo/U 0.6/1KV and below.

It is widely used in power transmission lines and electricity distribution lines with various voltage levels, because they have such good characteristics as simple structure, convenient installation and maintenance, low cost large transmission capacity. And they are also suitable for laying across rivers valleys and the places where special geographical features exist.


Standard

IEC 61089, BS 7870, DIN 48201, ASTM B399, BS EN50183, NFC33-209


Construction

Conductor: copper, aluminum,aluminum alloy;

Insulation:PVC,HDPE,XLPE


Technical data

Table 1 : Technology requirements of copper core ABC insulated cable

Nominal cross section area of conductor(mm²)Single wire Min. No of conductorConductor O.D.(reference value)/mmNominal thickness of insulation(mm)
1063.81
1664.81.2
25661.2
35671.4
5068.41.4
7012101.4
951511.61.6
12018131.6
1501814.61.8
1853016.22
2403418.42.2
The Max. Resistance of conductor at 20°C(Ω/km)The Min, resistance of insulation at rated temperatureBreaking load of single core
Hard copperSoft copper70°C90°CHard copper
1.9061.830.00670.673471
1.1981.150.00650.655486
0.7490.7270.00540.548465
0.540.5240.00540.5411731
0.3990.3870.00460.4616502
0.2760.2680.0040.423461
0.1990.1930.00390.3931759
0.1580.1530.00350.3539911
0.1280.1240.00350.3549505
0.10210.09910.00350.3561846
0.07770.07540.00340.3479823


Table 2: Technology requirements of aluminum core,aluminum alloy core ABC insulated cable

No.section area of conductor (mm²)Single wire Min. No Of conductorConductor O.D. (reference value)/mmCable Max. Average outer diameter(mm)
1063.86.5
1664.88
25669.4
356711
5068.412.3
70121014.1
951511.616.5
120151318.1
1501514.620.2
1853016.222.5
2403018.425.6
3003020.827.2
4005323.230.7
The Max. Resistance of conductor at 20°C  (Ω/km)The Min. resistance of insulation at rated temperatureBreaking load of single core
AlumiunmAluminum alloy70°C90°CAlumiunmAluminum alloy
3.083.5740.00670.6716502514
1.912.2170.00650.6525174022
1.21.3930.00540.5437626284
0.8681.0070.00540.5451778800
0.6410.7440.00460.46701112569
0.4430.5140.0040.41035417596
0.320.3710.00390.391372723880
0.2530.2940.00350.351733930164
0.2060.2390.00350.352103337706
0.1640.190.00350.352673246503
0.1250.1450.00340.343467960329
0.10.1160.00330.334334975411
0.07780.09040.00320.3255707100548

Recommended Products