Languages

BS 5308 RE-2Y(St)Y Instrument Cable

300V PE instrument cable, PE insulation, Aluminium/Polyester Tape screen, PVC Sheath, tinned copper instrument cable.

  • Product Details
  • FAQ
  • Reviews

Application

BS 5308 cables are designed to carry communication and control signals in a variety of installation types including those found in the petrochemical industry. The signals can be of analogue, data or voice type and from a variety of transducers such as pressure, proximity or microphone. Part 1 Type 1 cables are generally designed for indoor use and in environments where mechanical protection is not required. 


Standard

BS/PAS 5308, BS EN 60228, BS EN 6234, BS EN 50363, BS EN/IEC 60332-1, BS EN/IEC 60332-3-24.


Construction

Conductor: Annealed or tinned copper, sizes: 0.5mm^2 and 0.75mm^2 mulitistranded(Class 5), 0.5 mm^2, 1.0 mm^2 solid(Class 1), 1.5mm^2 or 2.5mm^2, multistranded(Class 2) to BS6360

Insulation: PE (Polyethylene) type 03 to BS6234

Pairing: Two insulated conductors uniformly twisted together with a lay not exceeding 100mm

Colour code: See technical information

Binder tape: PETP transparent tape

Collective screen: Aluminium/polyester tape is applied over the laid up pairs metallic side down in contact with tinned copper drain wire, 0.5mm^2

Outer sheath: PVC Sheath, type TM 1 or type 6 to BS 6746

Sheath colour: Black or blue


Technical data

Voltage Rating (Uo/U):300/500V

Operating temperature:-40C up to + 70C( fixed installation)

                                 0C to +50C(during operation )

Minimum bending radius:5 x overall diameter


Special version upon request

AmourGalvanized steel wire armour


Advantages

Anti-interference, anti-static, explosion-proof performance 


Dimensions and Weights



Number of PairsNumber and Diameter of WiresNominal Conductor Cross-Sectional AreaNominal Thickness of InsulationNominal Thickness of SheathNominal Diameter of CableApprox. Weight
no./mmmm²mmmmmmkg/km
21/0.80.50.50.99.795
51/0.80.50.51.213180
101/0.80.50.51.216.9310
151/0.80.50.51.319.7440
201/0.80.50.51.322.3560
301/0.80.50.51.527.1820
501/0.80.50.52351370
216/0.20.50.61.111.2110
516/0.20.50.61.214.5250
1016/0.20.50.61.319.3480
1516/0.20.50.61.522.6570
2016/0.20.50.61.525.7780
3016/0.20.50.61.7311020
5016/0.20.50.62.239.91680
21/1.1310.61.111.9200
51/1.1310.61.215.4290
101/1.1310.61.320.5580
151/1.1310.61.524.1780
201/1.1310.61.727.71010
301/1.1310.6233.71430
501/1.1310.62.242.52360
27/0.531.50.61.213.6250
57/0.531.50.61.317.7460
107/0.531.50.61.523.9760
157/0.531.50.61.7281020
207/0.531.50.6231.71350
307/0.531.50.62.238.61900
507/0.531.50.62.248.93060

Electrical specifications


Conductor Area Sizemm²0.50.50.7511.5
Conductor StrandingNo. x mm1 x 0.816 x 0.224 x 0.21 x 1.137 x 0.53
Conductor resistance maxohm/km36.839.726.518.212.3
Insulation resistance minGohm/km55555
Capacitance unbalance at 1 kHz(pair to pair screen)pF/250m250
Max. Mutual Capacitance @ 1 kHz forNon OS or OS cables (except one-pair and to-pairs)pF/m115115115115115
Max. Mutual Capacitance @ 1 kHz IS/OS cables (include 1 pair and 2 pair)pF/m7575757575
Max. L/R Ratio for adjacent cores(Inductance/ Resistance)μH/ohm2525252540
Test voltageCore to coreV10001000100010001000
Core to screenV10001000100010001000
Rated voltage maxV300/500300/500300/500300/500300/500