12/20 kV XLPE Insulated PVC Sheathed Power Cable

20kV XLPE insulated cable, XLPE Insulation, Copper cable, PVC Sheath, Power Cable

  • Product Details
  • FAQ
  • Reviews

Application

Currently XLPE insulation is a type of isolation that is very much its use because of its mechanical properties is quite good and does not suck water.


Standard

TS IEC 60502, BS 6622, VDE 0276, upon request.


Construction

1 Stranded copper conductor

2 Inner semi-conductive layer

3 XLPE in sulation

4 Outer semi-conductive layer

5 Semi-conductive tape

6 Copper wire screen

7 Polyester tape

8 PVC outer jacket


Technical data

Max. operating temperature: 90°C

Max. short circuit temperature: 250°C (max. 5 sn.)

Rated voltage: 8.7/15 kV

Min. bending radius: 15 x D

D: Cable outer diameter


Advantages

Due to a low dielectric loss factor and the strong XLPE insulation, this cable offers long-term operational reliability. Nevertheless, it should be used in fixed installations to avoid mechanical or tensile strain.


Electrical specifications

Number of cores and nominal cross section mm2Copper figure kg/kmOverall diameter appr. mmOverall diameter max. value appr. mmWeight appr. kg/kmCurrent carrying capacity ground ACurrent carrying capacity air A
1 x 35 RM/16540,0 27 32 1.100,0 189 200 
1 x 50 RM/16690,0 28 33 1.250,0 222 239 
1 x 70 RM/16890,0 30 35 1.450,0 271 297 
1 x 95 RM/161.140,0 31 36 1.750,0 323 361 
1 x 120 RM/161.390,0 33 38 2.050,0 367 416 
1 x 150 RM/251.795,0 34 39 2.400,0 409 470 
1 x 185 RM/252.145,0 36 41 2.800,0 461 538 
1 x 240 RM/252.695,0 39 44 3.400,0 532 634 
1 x 300 RM/253.295,0 41 46 4.000,0 599 724 
1 x 400 RM/354.410,0 44 49 4.950,0 671 829 
1 x 500 RM/355.410,0 47 52 6.050,0 754 953