Languages

21/35kV Armoured Cable

21/35kV XLPE insulated Steel Wire Armoured(Steel Tape Armoured)/ PVC sheathed power cable

  • Product Details
  • FAQ
  • Reviews

Application

To be used at 35,000 volts or less and at conductor temperatures not to exceed 90°C for normal operation.

It is generally applied to the fields including power, construction, mines, metallurgy, petrochemical industry and communication in complete replace of oil immersed paper insulated power cable.


Standard

IEC60502-1, BS 5467, and etc. upon request.


Construction

Conductor

Number of conductors:1,3

The conductors shall comply with the requirement given in IEC

Insulation

XLPE(Cross-linked Polyethylene) according to IEC

Sheath

PVC(Polyaluminium Chloride) according to IEC

Metal screen

Copper Tape Screen

Galvanized steel wire/ tape armoured (SWA/STA)

Sheath colour: Black


Technical data

Rated Voltage (Uo/U)

3.6/6KV

Conductor temperature

Maximum conductor temperature in normal use: 90℃

Max.short-circuit temperature

Maximum shall not exceed 250℃(5s Max,Duration)

Installation temperature

Ambient temperature under installation shall not be below 0℃

Minimum bending radius

The bending radius of cable: (D-Diameter of cable) 

For Three Core Cable————————————-≥15D

For Single Core Cable————————————-≥20D


Advantages

Strict quality control system.

Faster lead time than our competitors.


Electrical specifications

Size (sq.mm)Nominal thickness of XLPE insulation(mm)Approx. thickness of copper tape screen (mm)Approx. diameter of steel wire (mm)Nominal thickness of PVC or PE(mm)Approx. overall diameter of finished cable(mm)Max. conductor D.C resistance @ 20 0 C (Ω/km)
3x5010.50.103.153.892.30.387
3x7010.50.103.153.996.40.268
3x9510.50.103.154.1100.40.193
3x12010.50.103.154.2103.80.153
3x15010.50.103.154.3107.80.124
3x18510.50.103.154.4111.50.0991
3x24010.50.103.154.6117.30.0754
3x30010.50.103.154.7122.10.0601
3x40010.50.103.155.0130.00.0470